Skip to content

Battery Energy Storage System Fire Safety Narrative - Tamsin Ridge

C-76f3e4d772 · Page 2 of 2 · DR-0014 · 2023-06-28

The claim, in the assessor's words

The BESS yard is 150 feet from the nearest property line and 610 feet from the nearest residence (R-6).

Quoted from page 2
The yard is 150 feet from the nearest property line and 610 feet from the nearest residence (R-6).

Source consultant_memo · Claim type study_finding · Polarity neutral · Confidence high · Quote check exact, 100 of 100

Cited by EG-04 Battery Storage Fire Safety · Filed under CO-02, EG-04

On the page

The page text exactly as the engine read it, with the quote marked.

Placed normalised · The quote matches the page once line breaks, hyphenation, case and punctuation are set aside, as the engine's matcher compares text. The marked words are the page's own.

Read as native

Go to the marked quote

BESS Fire Safety Narrative - Tamsin Ridge Solar and Storage Project 5. Siting and separation Enclosures are spaced 10 feet apart in rows with 25-foot aisles. Quote starts. The yard is 150 feet from the nearest property line and 610 feet from the nearest residence (R-6). Quote ends. The substation is 60 feet from the yard. Heat flux modeling of a single enclosure fully involved in fire shows less than 12.6 kW per square meter at the fence and at the adjacent enclosure rows. 6. Fire department access and water A 20-foot all-weather access road circles the yard, with two gates and a turnaround. There are no fire hydrants in the area; the nearest pressurized water is in Carrollton, about 4 miles away. A 30,000-gallon firefighting water storage tank with a dry hydrant connection is planned at the yard entrance for exposure protection. The first-due fire department is a volunteer department about 5 miles away with two engines and one tanker. It has not yet reviewed the design or the response plan. 7. Emergency response A draft emergency response plan covers alarm notification, the 24-hour remote operations center with central station monitoring, shutdown procedures, defensive tactics (protect exposures, let an involved enclosure burn out, do not open its doors), air monitoring downwind, and post-incident handling of damaged batteries. It will be completed with the fire department and the Carroll County Emergency Management Agency before the OPSB application, and training will be offered to the fire department before commissioning. 8. Open items • Confirm the code edition and permit path with the State Fire Marshal and the local fire code official. • Obtain fire department review of access, water supply and tactics, and complete the emergency response plan. • Obtain large-scale fire test data from the manufacturer, if OPSB staff or the fire department request it. • Plan for battery removal and recycling at end of life in the decommissioning plan. Hollis Brandt, P.E., Fire Protection Engineer, Tallis Fire Engineering, LLC. Tallis Fire Engineering, LLC - Report TFE-2306 Page 2 of 2

The page

The outline marks where the quote begins on the page.

Page 2 of Battery Energy Storage System Fire Safety Narrative - Tamsin Ridge

Other claims quoted on this page

  • C-d757c50e61

    Heat flux modeling of a single fully involved enclosure shows less than 12.6 kW per square meter at the fence and adjacent enclosure rows.

  • C-04a3f6e338

    There are no fire hydrants near the yard; the nearest pressurized water is in Carrollton, about 4 miles away.

  • C-08b9d4306e

    The first-due volunteer fire department, about 5 miles away with two engines and one tanker, has not yet reviewed the design or response plan.

  • C-640e804855

    Plan for battery removal and recycling at end of life in the decommissioning plan.

Lumerian Labs 2026