Battery Energy Storage System Fire Safety Narrative - Tamsin Ridge
C-b6407da087 · Page 1 of 2 · DR-0014 · 2023-06-28
The claim, in the assessor's words
No large-scale fire test beyond UL 9540A has been performed for this enclosure.
No large-scale fire test beyond UL 9540A has been performed for this enclosure
Source consultant_memo · Claim type absence · Polarity absence · Confidence high · Quote check exact, 100 of 100
Cited by EG-04 Battery Storage Fire Safety · Filed under EG-04
On the page
The page text exactly as the engine read it, with the quote marked.
Placed verbatim · The quote occurs on the page exactly as written.
Read as native
The page
The outline marks where the quote begins on the page.

Other claims quoted on this page
The selected enclosure is listed to UL 9540 as an energy storage system.
In the UL 9540A unit-level test, thermal runaway in one module did not spread to adjacent modules and no flaming occurred outside the enclosure.
Design follows NFPA 855 (2020 edition) and the Ohio Fire Code energy storage provisions as adopted by the State Fire Marshal.
The governing code edition and whether the local fire code official will require a construction permit for an OPSB-certificated facility have not been confirmed.
The OPSB application must include a fire protection, safety and medical emergency plan developed with local responders.
A hazard mitigation analysis using FMEA was completed for the enclosure design.
There is no internal fire suppression in the enclosures; design relies on containment, spacing, explosion control and defensive firefighting.